diff --git a/content/hardware/07.opta/opta-family/opta/datasheet/datasheet.md b/content/hardware/07.opta/opta-family/opta/datasheet/datasheet.md index aad8166b12..99e5edd4b2 100644 --- a/content/hardware/07.opta/opta-family/opta/datasheet/datasheet.md +++ b/content/hardware/07.opta/opta-family/opta/datasheet/datasheet.md @@ -429,11 +429,11 @@ Arduino Opta® is designed for industrial standard machinery control as a PLC wi ## Ratings ### Recommended Operating Conditions -| Description | Value | -|---------------------------------------------------|---------------------------| -| Temperature Operating Range | -20...50 °C | -| Protection degree rating | IP20 | -| Pollution degree | 2 conforming to IEC 61010 | +| Description | Value | +| --------------------------- | ------------------------- | +| Temperature Operating Range | -20...50 °C | +| Protection degree rating | IP20 | +| Pollution degree | 2 conforming to IEC 61010 | ### Power Specification @@ -457,7 +457,7 @@ Arduino Opta® is designed for industrial standard machinery control as a PLC wi | 3A | Power Supply Terminals 12...24 VDC | 3H | Ethernet Port Status LEDs | | 3B | I1...I8 digital/analog input terminals (0-10V) configurable via IDE | 3I | Label Holder | | 3C | Reset Button | 3J | RS-485 terminal block (for Modbus RTU or proprietary communication) | -| 3D | User Programmable button | 3K | USB-C® for programming and data logging | +| 3D | User Programmable button | 3K | USB-C® for programming and data logging | | 3E | Status LEDs 1...4 (User Programmable) | 3M | Ethernet port | | 3F | Relay Output Terminals 1...4, NO contact (SPST) 10A 250 VAC | 3N | Port for communication and connection of auxiliary modules | | 3G | Functional Earth | | | @@ -539,6 +539,18 @@ Now that you have gone through the basics of what you can do with the device, yo
+## Mean Time Between Failure (MTBF) + +MTBF, which stands for Mean Time Between Failure, is calculated according to statistical device failures and indicates the reliability of a device. + +The MTBF figure (in hours/years) for each Arduino Opta® variant can be found in the table below. The MTBF figure was calculated according to the MIL-HDBK-217F parts count method. + +| **Standard** | **All Opta® Variants** | **Environmental Conditions** | +|:-------------:|:----------------------:|:----------------------------:| +| MIL-HDBK-217F | 766205 h/87 years | 25 ºC | + +**Important note**: MTBF is the statistical representation of the likelihood of a unit failing and _does not necessarily represent a product's life_. + ## Mechanical Information ### Product Dimensions ![Arduino Opta® Outline. Dimensions are in mm](assets/opta_mechanical.svg) @@ -750,8 +762,9 @@ Hereby, Arduino S.r.l. declares that this product is in compliance with essentia ## Revision History -| Date | **Revision** | **Changes** | -|------------|--------------|------------------- | -| 16/05/2023 | 3 | Legal updates | -| 13/04/2023 | 2 | Tech Specs Updates | -| 02/03/2023 | 1 | First Release | +| Date | **Revision** | **Changes** | +|------------|:------------:|:------------------:| +| 07/02/2023 | 4 | MTBF information | +| 16/05/2023 | 3 | Legal updates | +| 13/04/2023 | 2 | Tech Specs Updates | +| 02/03/2023 | 1 | First Release | \ No newline at end of file diff --git a/content/hardware/07.opta/opta-family/opta/downloads/AFX00001-AFX00002-AFX00003-datasheet.pdf b/content/hardware/07.opta/opta-family/opta/downloads/AFX00001-AFX00002-AFX00003-datasheet.pdf new file mode 100644 index 0000000000..ccbe6cdfb4 Binary files /dev/null and b/content/hardware/07.opta/opta-family/opta/downloads/AFX00001-AFX00002-AFX00003-datasheet.pdf differ